Setting jumpers, Install the module in the rack – ProSoft Technology MVI56E-MNETR User Manual

Page 12

Advertising
background image

MVI56E-MNETR ♦ ControlLogix Platform

Start Here

Modbus TCP/IP Interface Module with Reduced Data Block

User Manual


Page 12 of 153

ProSoft Technology, Inc.

August 31, 2009

1.4 Setting

Jumpers

The Setup Jumper acts as "write protection" for the module’s flash memory. In
"write protected" mode, the Setup pins are not connected, and the module’s
firmware cannot be overwritten. Do not jumper the Setup pins together unless
you are directed to do so by ProSoft Technical Support.

The following illustration shows the MVI56E-MNETR jumper configuration.

Note: If you are installing the module in a remote rack, you may prefer to leave the Setup pins
jumpered. That way, you can update the module’s firmware without requiring physical access to
the module.

1.5

Install the Module in the Rack

If you have not already installed and configured your ControlLogix processor and
power supply, please do so before installing the MVI56E-MNETR module. Refer
to your Rockwell Automation product documentation for installation instructions.

Warning: You must follow all safety instructions when installing this or any other electronic
devices. Failure to follow safety procedures could result in damage to hardware or data, or even
serious injury or death to personnel. Refer to the documentation for each device you plan to
connect to verify that suitable safety procedures are in place before installing or servicing the
device.

After you have checked the placement of the jumpers, insert the MVI56E-
MNETR into the ControlLogix chassis. Use the same technique recommended by
Rockwell Automation to remove and install ControlLogix modules.

You can install or remove ControlLogix system components while chassis power
is applied and the system is operating. However, please note the following
warning.