Float start, Float offset, Arp timeout – ProSoft Technology MVI56E-MNETR User Manual

Page 56: Command error delay

Advertising
background image

MVI56E-MNETR ♦ ControlLogix Platform

Configuring the MVI56E-MNETR Module

Modbus TCP/IP Interface Module with Reduced Data Block

User Manual


Page 56 of 153

ProSoft Technology, Inc.

August 31, 2009

gateway address 3999 (virtual Modbus address 44000 or 440000). When set to
Y

ES

, the Slave driver will return values from two, consecutive, 16-bit internal

memory registers (32 total bits) for each count in the read command or receive
32-bits per count from the Master for write commands. Example: Count = 10,
Slave driver will send 20 16-bit registers for 10 total 32-bit floating-point values.

If, however, the remote Master sends a count of two (2) for each 32-bit floating-
point value it expects to receive or send, or, if you do not plan to use floating-
point data in your application, then set this parameter to N

O

, which is the default

setting.

You will also need to set the Float Start and Float Offset parameters to
appropriate values whenever the Float Flag parameter is set to Y

ES

.

Float Start

0 to 65535

This parameter defines the first register of floating-point data. All requests with
register values greater-than or equal to this value will be considered floating-point
data requests. This parameter is only used if the Float Flag is enabled. For
example, if a value of 7000 is entered, all requests for registers 7000 and above
will be considered as floating-point data.

Float Offset

0 to 9999

This parameter defines the start register for floating-point data in the internal
database. This parameter is used only if the Float Flag is enabled. For example,
if the Float Offset value is set to 3000 and the float start parameter is set to 7000,
data requests for register 7000 will use the internal Modbus register 3000.

ARP Timeout

1 to 60

This parameter specifies the number of seconds to wait for an ARP reply after a
request is issued.

Command Error Delay

0 to 300

This parameter specifies the number of 100 millisecond intervals to turn off a
command in the error list after an error is recognized for the command. If this
parameter is set to 0, there will be no delay.

Advertising
This manual is related to the following products: