Sub-function codes supported, 00 return query data, Example and state diagram – ProSoft Technology MVI56E-MNETR User Manual

Page 127

Advertising
background image

Reference MVI56E-MNETR

♦ ControlLogix Platform

User Manual

Modbus TCP/IP Interface Module with Reduced Data Block


ProSoft Technology, Inc.

Page 127 of 153

August 31, 2009

Request

Function code

1 Byte

0x08

Sub-function 2

Bytes

Data

N x 2 Bytes

Response

Function code

1 Byte

0x08

Sub-function 2

Bytes

Data

N x 2 Bytes

Error

Error code

1 Byte

0x88

Exception code

1 Byte

01 or 03 or 04

Sub-function codes supported

Only Sub-function 00 is supported by the MVI56E-MNETR module.

00 Return Query Data

The data passed in the request data field is to be returned (looped back) in the
response. The entire response message should be identical to the request.

Sub-function

Data Field (Request)

Data Field (Response)

00 00

Any

Echo Request Data

Example and state diagram

Here is an example of a request to remote device to Return Query Data. This
uses a sub-function code of zero (00 00 hex in the two-byte field). The data to be
returned is sent in the two-byte data field (A5 37 hex).

Request

Response

Field Name

(Hex)

Field Name

(Hex)

Function 08

Function 08

Sub-function Hi

00

Sub-function Hi

00

Sub-function Lo

00

Sub-function Lo

00

Data Hi

A5

Data Hi

A5

Data Lo

37

Data Lo

27