MVI56E-MNETR ♦ ControlLogix Platform

Start Here

Modbus TCP/IP Interface Module with Reduced Data Block

User Manual


Page 30 of 153

ProSoft Technology, Inc.

August 31, 2009

3 Set the Module Properties values as follows:

Parameter Value

Name

Enter a module identification string. The recommended value is
MNETR.

Description

Enter a description for the module. Example: Modbus TCP/IP
Interface Module with Reduced Data Block.

Comm Format

Select D

ATA

-INT

(Very Important)

Slot

Enter the slot number in the rack where the MVI56E-MNETR
module is or will be located.

Input Assembly Instance

1

Input Size

42

Output Assembly Instance

2

Output Size

42

Configuration Assembly Instance 4

Configuration Size

0

4 On the C

ONNECTION

tab, set the RPI

value for your project. Fifty (50)

milliseconds is usually a good starting value.