Configuration error word – ProSoft Technology MVI56E-MNETR User Manual

Page 98

Advertising
background image

MVI56E-MNETR ♦ ControlLogix Platform

Diagnostics and Troubleshooting

Modbus TCP/IP Interface Module with Reduced Data Block

User Manual


Page 98 of 153

ProSoft Technology, Inc.

August 31, 2009

Operation Messages

After the initialization step, the following message pattern will be repeated.

<Backplane Status> <IP Address> <Backplane Status> <Port Status>

Code Message

<Backplane Status>

OK: Module is communicating with processor

ERR: Module is unable to communicate with processor. For
this scenario, the <Port Status> message above is replaced
with "Processor faulted or is in program mode".

<IP Address>

Module IP address

<C0>

OK: Port is communicating without error

Communication Errors: port is having communication errors.
Refer to PCB diagnostics for further information about the
error.

The LEDs indicate the module's operating status as follows:

Module Color

Status

Indication

On

The MVI56E-MNETR is working normally.

APP Amber

Off

The MVI56E-MNETR module program has recognized a
communication error on its Application Port(s).

Off

The card is not receiving adequate power, or is not securely
plugged into the rack.

Green

The module is operating normally.

OK

Red/
Green

Red

The module has detected an internal error, or is being
initialized. If the LED remains red for over 10 seconds, the
module is not working. Remove it from the rack and re-insert it
to restart its internal program.

Off

The battery voltage is OK and functioning.

BAT Red

On

The battery voltage is low, or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user-serviceable item.

4.9.1 Configuration

Error

Word

If a configuration error is found for the Client, the Client configuration error word
will have a value other than zero. The configuration error word bits have the
following definitions:

Bit Description

Value

0

0x0001

1

0x0002

2

0x0004

3

0x0008

4

Invalid retry count parameter

0x0010

5

The float flag parameter is not valid.

0x0020

6

The float start parameter is not valid.

0x0040

7

The float offset parameter is not valid.

0x0080

Advertising