Node ip address, Service port, Slave address – ProSoft Technology MVI56E-MNETR User Manual

Page 61: Modbus function

Advertising
background image

Configuring the MVI56E-MNETR Module

MVI56E-MNETR ♦ ControlLogix Platform

User Manual

Modbus TCP/IP Interface Module with Reduced Data Block


ProSoft Technology, Inc.

Page 61 of 153

August 31, 2009

Node IP Address

xxx.xxx.xxx.xxx

The IP address of the device being addressed by the command.

Service Port

502 or other supported ports on server

Use a value of 502 when addressing Modbus TCP/IP servers that are compatible
with the Schneider Electric MBAP specifications (this will be most devices). If a
server implementation supports another service port, enter the value here.

Slave Address

0 - Broadcast to all nodes

1 to 255

Use this parameter to specify the slave address of a remote Modbus Serial
device through a Modbus Ethernet to Serial converter.

Note: Use the Node IP Address parameter (page 61) to address commands to a remote Modbus
TCP/IP device.
Note: Most Modbus devices accept an address in the range of only 1 to 247, so check with slave
device manufacturer to see if a particular slave can use addresses 248-255.
If the value is set to zero, the command will be a broadcast message on the network. The Modbus
protocol permits broadcast commands for write operations. Do not use node address 0 for read
operations.

Modbus Function

1, 2, 3, 4, 5, 6, 15, or 16

This parameter specifies the Modbus Function Code to be executed by the
command. These function codes are defined in the Modbus protocol. The
following table lists the purpose of each function supported by the module. More
information on the protocol is available from www.modbus.org.

Modbus Function Code

Description

1

Read Coil Status

2

Read Input Status

3 Read

Holding

Registers

4

Read Input Registers

5

Force (Write) Single Coil

6

Preset (Write) Single Register

15 Force

Multiple

Coils

16

Preset Multiple Registers

Advertising
This manual is related to the following products: