MVI56E-MNETR ♦ ControlLogix Platform

Configuring the MVI56E-MNETR Module

Modbus TCP/IP Interface Module with Reduced Data Block

User Manual


Page 58 of 153

ProSoft Technology, Inc.

August 31, 2009

Command Entry Formats

The following table shows the structure of the configuration data necessary for
each of the supported commands.

Column
#

1 2

3 4 5 6 7 8 9

10

Function
Code

Enable
Code

Internal
Address

Poll
Interval
Time

Count Swap

Code

IP
Address

Serv
Port

Slave
Node

Function
Code

Device
Modbus
Address

fc1 Code

Register
(bit)

1/10th
Seconds

Bit
Count

0 IP

Address

Port # Address Read Coil

(0x)

Register

fc2 Code

Register
(bit)

1/10th
Seconds

Bit
Count

0 IP

Address

Port # Address Read Input

(1x)

Register

fc3 Code

Register

1/10th
Seconds

Word
Count

Code IP

Address

Port # Address Read Holding

Registers
(4x)

Register

fc4 Code

Register

1/10th
Seconds

Word
Count

0 IP

Address

Port # Address Read Input

Registers
(3x)

Register

fc5 Code

1

bit 1/10th

Seconds

Bit
Count

0 IP

Address

Port # Address Force (Write)

Single Coil
(0x)

Register

fc6 Code

1

bit 1/10th

Seconds

Word
Count

0 IP

Address

Port # Address Preset (Write)

Single
Register (4x)

Register

fc15 Code

Register
(bit)

1/10th
Seconds

Bit
Count

0 IP

Address

Port # Address Force (Write)

Multiple Coil
(0x)

Register

fc16 Code

Register

1/10th
Seconds

Word
Count

0 IP

Address

Port # Address Preset (Write)

Multiple
Register (4x)

Register

The first part of the record is the module Information, which relates to the
MVI56E module and the second part contains information required to interface to
the Server device.