Important safety information - mvi56e modules – ProSoft Technology MVI56E-MNETR User Manual

Page 2

Advertising
background image

Important Safety Information - MVI56E Modules

North America Warnings

A

Warning - Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2.

B

Warning - Explosion Hazard - When in Hazardous Locations, turn off power before replacing or rewiring
modules.
Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is
known to be nonhazardous.

C

Suitable for use in Class I, Division 2 Groups A, B, C, and D, T5 Hazardous Locations or Non-Hazardous
Locations.

ATEX Warnings and Conditions of Safe Usage

Power, Input, and Output (I/O) wiring must be in accordance with the authority having jurisdiction

A

Warning - Explosion Hazard - When in hazardous locations, turn off power before replacing or wiring modules.

B

Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is
known to be non-hazardous.

C

These products are intended to be mounted in an IP54 enclosure. The devices shall provide external means to
prevent the rated voltage being exceeded by transient disturbances of more than 40%. This device must be used
only with ATEX certified backplanes.

D

DO NOT OPEN WHEN ENERGIZED.

Electrical Ratings

ƒ

Backplane Current Load: 800 mA @ 5 V DC; 3mA @ 24V DC

ƒ

Operating Temperature: 0 to 60°C (32 to 140°F)

ƒ

Storage Temperature: -40 to 85°C (-40 to 185°F)

ƒ

Shock: 30g Operational; 50g non-operational; Vibration: 5 g from 10 to 150 Hz

ƒ

Relative Humidity 5% to 95% (non-condensing)

ƒ

All phase conductor sizes must be at least 1.3 mm (squared) and all earth ground conductors must be at least
4mm (squared).

Markings

ANSI / ISA

ISA 12.12.01 Class I Division 2, GPs A, B, C, D

CSA/cUL

C22.2 No. 213-M1987

CSA CB Certified

IEC61010

ATEX

EN60079-0 Category 3, Zone 2

EN60079-15

243333

E183151

CL I Div 2 GP A, B, C, D

Temp Code T5

II 3 G

Ex nA nL IIC T5 X

0° C <= Ta <= 60° C

II – Equipment intended for above ground use (not for use in mines).

3 – Category 3 equipment, investigated for normal operation only.

G – Equipment protected against explosive gasses.

Advertising
This manual is related to the following products: