12. OPTIONS AND AUXILIARY EQUIPMENT

(2) Selection example

Indicated below is an example of selecting a leakage current breaker under the following conditions.

M

Servo
amplifier
MR-J2S-60B

Servo motor
HC-MFS73

Ig1

Ig2

Iga

Igm

NV

2mm

2

5m

2mm

2

5m

Use a leakage current breaker designed for suppressing harmonics/surges.
Find the terms of Equation (12.1) from the diagram.

Ig1 20

1000

5

0.1 [mA]

Ig2 20

1000

5

0.1 [mA]

Ign 0 (not used)

Iga 0.1 [mA]

Igm 0.1 [mA]

Insert these values in Equation (12.1).

Ig 10 {0.1 0 0.1 1 (0.1 0.1)}

4 [mA]

According to the result of calculation, use a leakage current breaker having the rated sensitivity
current (Ig) of 4[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-
SP/CP/SW/CW/HW series.