3 - 14

3. SIGNALS AND WIRING

3.5 Power line circuit

CAUTION

Always connect a magnetic contactor (MC) between the main circuit power supply

and L

1

,

L

2

,

and L

3

of the servo amplifier, and configure the wiring to be able to shut

down the power supply on the side of the servo amplifier’s power supply. If a
magnetic contactor (MC) is not connected, continuous flow of a large current may
cause a fire when the servo amplifier malfunctions.

Switch power off at detection of an alarm. Otherwise, a regenerative transistor fault

or the like may overheat the regenerative resistor, causing a fire.

POINT

For the power line circuit of the MR-J2S-11KB to MR-J2S-22KB, refer to
section 3.12 where the power line circuit is shown together with the servo
motor connection diagram.

3.5.1 Connection example

Wire the power supply/main circuit as shown below so that power is shut off and the servo-on command
turned off as soon as an alarm occurs, a servo forced stop is made valid, or a controller forced stop is made
valid. A no-fuse breaker (NFB) must be used with the input cables of the power supply.

(1) For 3-phase 200 to 230V power supply

EM1

COM

OFF

ON

MC

MC

SK

NFB

MC

L

1

L

2

L

3

L

11

L

21

VDD

SG

(Note 2)

Alarm

RA1

Controller

forced stop

RA2

Forced

stop

Servo amplifier

Forced stop

(Note 1)

P

P

1

Power supply
3-phase
200 to 230V

Note 1. Make sure to connect P

1

-P. (Factory-wired.) When using the power factor improving DC reactor, refer to section 12.2.4.

2. Configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the

controller side.