3. SIGNALS AND WIRING

3.5.2 Terminals

The positions and signal arrangements of the terminal blocks change with the capacity of the servo
amplifier. Refer to section 10.1.

Symbol

Connection Target

(Application)

Description

Supply L

1

, L

2

and L

3

with the following power.

For 1-phase 230V, connect the power supply to L

1

/L

2

and leave L

3

open.

Servo amplifier

Power supply

MR-J2S-10B to

70B

MR-J2S-100B

to 22K

MR-J2S-10B1

to 40B1

3-phase 200 to 230VAC,
50/60Hz

L

1

L

2

L

3

1-phase 230VAC,
50/60Hz

L

1

L

2

1-phase 100 to 120VAC,
50/60Hz

L

1

L

2

L

1

, L

2

, L

3

Main circuit power supply

U, V, W

Servo motor output

Connect to the servo motor power supply terminals (U, V, W). During power-on, do
not open or close the motor power line. Otherwise, a malfunction or faulty may
occur.

P

1

Power factor improving DC

reactor

When not using the power factor improving DC reactor, connect P

1

and P.

(Factory-wired.)
When using the power factor improving DC reactor, disconnect the wiring across
P

1

-P and connect the power factor improving DC reactor across P

1

-P.

Refer to section 11.2.4.
Supply the following power to L

11

, L

21

.

Servo amplifier

Power supply

MR-J2S-10B to 700B

MR-J2S-10B1 to 40B1

1-phase 200 to 230VAC,
50/60Hz

L

11

L

21

1-phase 100 to 120VAC,
50/60Hz

L

11

L

21

L

11

, L

21

Control circuit power supply

P, C, D

Regenerative option

1) MR-J2S-350B or less

When using servo amplifier built-in regenerative resistor, connect between P
and D terminals. (Wired by default)
When using regenerative option, disconnect between P-D terminals and connect
regenerative option to P terminal and C terminal.

2) MR-J2S-500B and 700B

MR-J2S-500B and 700B do not have D terminal.
When using servo amplifier built-in regenerative resistor, connect P terminal
and C terminal. (Wired by default)
When using regenerative option, disconnect P terminal and C terminal and
connect regenerative option to P terminal and C terminal.
Refer to section 12.1.1.

3) MR-J2S-11KB to 22KB

MR-J2S-11KB to 22KB do not have D terminal.

When not using the power supply return converter and the brake unit, make

sure to connect the regenerative option to P terminal and C terminal.

Refer to section 12.1.1.

N

Return converter

Brake unit

When using return converter/brake unit, connect to P terminal and N terminal.
Do not connect to servo amplifier MR-J2S-200B or less.
For details, refer to section 12.1.2 to 12.1.3.

Protective earth (PE)

Connect this terminal to the protective earth (PE) terminals of the servo motor
and control box for grounding.