3 - 26

3. SIGNALS AND WIRING

3.8 Grounding

WARNING

Ground the servo amplifier and servo motor securely.

To prevent an electric shock, always connect the protective earth (PE) terminal

( ) of the servo amplifier with the protective earth (PE) of the control box.

The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on
the wiring and ground cable routing, the servo amplifier may be affected by the switching noise (due to
di/dt and dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always
ground.
To conform to the EMC Directive, refer to the EMC Installation Guidelines (IB(NA)67310).

L

1

L

2

L

3

L

11

L

21

CN1A

NFB

MC

CN2

U
V

W

M

U

V

W

(Note 2)

Control box

Servo amplifier

Li

ne

filt

er

Protective earth (PE)

Outer
box

Servo motor

Encoder

Pr

og

ra

mma

bl

e

co

nt

ro

ller

Ensure to connect it to PE
terminal of the servo amplifier.
Do not connect it directly
to the protective earth of
the control panel.

(Note 1)
Power supply

Note 1. For 1-phase 230V, connect the power supply to L

1

L

2

and leave L

3

open.

There is no L

3

for 1-phase 100 to 120V power supply. Refer to section 1.3 for the power supply specification.

2. To reduce the influence of external noise, we recommend you to ground the bus cable near the controller using a cable

clamping fixture or to connect three or four data line filters in series.