2 servo amplifier terminals, Signals and wiring – MITSUBISHI ELECTRIC Merservo MR-J2S- B User Manual

Page 77

Advertising
background image

3 - 34

3. SIGNALS AND WIRING

3.12.2 Servo amplifier terminals

The positions and signal arrangements of the terminal blocks change with the capacity of the servo
amplifier. Refer to section 10.1.

Symbol

Connection Target

(Application)

Description

L

1

, L

2

, L

3

Main circuit power supply

Supply L

1

, L

2

and L

3

with three-phase 200 to 230VAC, 50/60Hz power.

U, V, W

Servo motor output

Connect to the servo motor power supply terminals (U, V, W).

L

11

, L

21

Control circuit power supply Supply L

11

and L

21

with single-phase 200 to 230VAC power.

P, C

Regenerative option

The servo amplifier built-in regenerative resistor is not connected at the time of
shipment.
When using the regenerative option, wire it across P-C.
Refer to section 12.1.1 for details.

N

Return converter

Brake unit

When using the return converter or brake unit, connect it across P-N.
Refer to sections 12.1.2 and 12.1.3 for details.

Protective earth (PE)

Connect this terminal to the protective earth (PE) terminals of the servo motor
and control box for grounding.

P

1

, P

Power factor improving DC

reactors

P

1

-P are connected before shipment. When connecting a power factor improving

DC reactor, remove the short bar across P

1

-P. Refer to section 12.2.4 for details.