2 earth (grounding) requirements, 1 leakage current (>3,5ma), Warning – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 15

Advertising
background image

2.4.2 Earth (Grounding) Requirements

WARNING

GROUNDING HAZARD!

For operator safety, it is important to ground drive
properly in accordance with national and local electrical
codes as well as instructions contained within these
instructions. Ground currents are higher than 3,5mA.
Failure to ground drive properly could result in death or
serious injury.

NOTE

It is the responsibility of the user or certified electrical
installer to ensure correct grounding (earthing) of the
equipment in accordance with national and local electrical
codes and standards.

Follow all local and national electrical codes to
ground electrical equipment properly

Proper protective grounding for equipment with
ground currents higher than 3,5mA must be
established, see Leakage Current (>3,5mA)

A dedicatedground wire is required for input
power, motor power and control wiring

Use the clamps provided with on the equipment
for proper ground connections

Do not ground one drive to another in a “daisy
chain” fashion

Keep the ground wire connections as short as
possible

Use of high-strand wire to reduce electrical noise
is recommended

Follow motor manufacturer wiring requirements

2.4.2.1 Leakage Current (>3,5mA)

Follow national and local codes regarding protective
earthing of equipment with a leakage current > 3,5mA.
Drive technology implies high frequency switching at high
power. This will generate a leakage current in the earth
connection. A fault current in the drive at the output
power terminals might contain a DC component which can
charge the filter capacitors and cause a transient earth
current. The earth leakage current depends on various
system configurations including RFI filtering, screened
motor cables, and drive power.

EN/IEC61800-5-1 (Power Drive System Product Standard)
requires special care if the leakage current exceeds 3,5mA.
Earth grounding must be reinforced in one of the
following ways:

Earth ground wire of at least 10mm

2

Two separate earth ground wires both complying
with the dimensioning rules

See EN 60364-5-54 § 543.7 for further information.

Using RCDs
Where residual current devices (RCDs), also known as earth
leakage circuit breakers (ELCBs), are used, comply with the
following:

Use RCDs of type B only which are capable of
detecting AC and DC currents

Use RCDs with an inrush delay to prevent faults
due to transient earth currents

Dimension RCDs according to the system configu-
ration and environmental considerations

Installation

AF-600 FP Operating Instructions

12