Parameters

Function

Setting

E-02 Terminal 19

Digital Input

[1] Reset

* = Default Value

Notes/comments:

Table 6.8 External Alarm Reset

Parameters

Function

Setting

AN-10 Terminal

53 Low Voltage

0.07V*

AN-11 Terminal

53 High Voltage

10V*

AN-14 Terminal

53 Low Ref./

Feedb. Value

0*

AN-15 Terminal

53 High Ref./

Feedb. Value

50*.

* = Default Value

Notes/comments:

Table 6.9 Speed Reference (using a manual potentiometer)

Parameters

Function

Setting

E-01 Terminal 18

Digital Input

[8] Start*

E-02 Terminal 19

Digital Input

[52] Run

Permissive

E-03 Terminal 27

Digital Input

[7] External

Interlock

E-24 Function

Relay

[167] Start

command

act.

* = Default Value

Notes/comments:

Table 6.10 Run Permissive

Hand Off Auto (HOA), without the use of the Drive keypad
To have a HOA system with an external 0-10V potenti-
ometer for the hand reference and a 4-20mA signal for the
auto reference, 2 set-ups should be used. In this example
set-up 1 is used for the hand mode and set-up 2 for the
auto mode. Analog input 53 is used for the hand reference
(0-10V potentiometer) and analog input 54 for the auto
reference (4-20mA) and digital input 27 for the set-up
selector. Please ensure that the analog inputs have the
correct dip settings (A-53 [U] and A-54 [I]).

In the upper right corner of the keypad 2 numbers are
shown – like 1(1). The number outside the parenthesis is
the active set-up and the number inside the parenthesis is
the set-up which will be edited. Default will always be 1(1).
Make sure you edit set-up 1.

1.

Make all the parameter changes you need, that
will be common for auto and hand mode, like
motor parameters etc.

2.

Set par. K-10 Active set-up to [9] Multi Set-up.
This parameter change is needed to be able to
change set-up from an external source, like a
digital input.

3.

Set par. K-11 Edit Set-up to [9] Active Set-up. This
is recommended because then the active setup

Application Set-Up Examples

AF-600 FP Operating Instructions

43

6

6