Parameters
Function
Setting
F-10 Electronic
Overload
[2]
Thermistor
trip
F-12 Motor
Thermistor Input
[1] Analog
input 53
* = Default Value
Notes/comments:
If only a warning is desired,
F-10 Electronic Overload should
be set to [1] Thermistor warning.
Table 6.13 Motor Thermistor
Parameters
Function
Setting
E-02 Terminal 19
Digital Input
[37] Fire
mode
FB-00 Fire Mode
Function
[0] Disabled*
FB-01 Fire Mode
Configuration
[0] Open
Loop*
FB-02 Fire Mode
Unit
[3] Hz*
FB-03 Fire Mode
Min Reference
0Hz*
FB-04 Fire Mode
Max Reference
50Hz*
FB-05 Fire Mode
Preset Reference
0%*
FB-06 Fire Mode
Reference Source
[0] No
function*
FB-07 Fire Mode
Feedback Source
[0] No
function*
FB-09 Fire Mode
Alarm Handling
[1] Trip,
Critical
Alarms*
* = Default Value
Notes/comments:
Parameters to setup Fire Mode
are all in the FB-## group.
Table 6.14 Fire Mode
Application Set-Up Examples
AF-600 FP Operating Instructions