Troubleshooting:

Check for proper fan operation.

Cycle power to the drive and check that the fan
operates briefly at start up.

Check the sensors on the heatsink and control
card.

WARNING 24, External fan fault
The fan warning function is an extra protective function
that checks if the fan is running/mounted. The fan warning
can be disabled in SP-53 Fan Monitor ([0] Disabled).

Troubleshooting:

Check for proper fan operation.

Cycle power to the drive and check that the fan
operates briefly at start up.

Check the sensors on the heatsink and control
card.

ALARM 29, Heatsink temp
The maximum temperature of the heatsink has been
exceeded. The temperature fault will not reset until the
temperature falls below a defined heatsink temperature.
The trip and reset points are different based on the drive
power size.

Troubleshooting:

Check for the following conditions.

Ambient temperature too high.

Motor cable too long.

Incorrect airflow clearance above and below the
drive

Blocked airflow around the drive.

Damaged heatsink fan.

Dirty heatsink.

ALARM 30, Motor phase U missing
Motor phase U between the drive and the motor is
missing.

Remove power from the drive and check motor phase U.

ALARM 31, Motor phase V missing
Motor phase V between the drive and the motor is
missing.

Remove power from the drive and check motor phase V.

ALARM 32, Motor phase W missing
Motor phase W between the drive and the motor is
missing.

Remove power from the drive and check motor phase W.

ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period. Let the unit cool to operating temperature.

WARNING/ALARM 34, communication fault
The network on the communication option card is not
working.

WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the drive is lost and SP-10 Line failure is NOT set to [0] No
Function
. Check the fuses to the drive and mains power
supply to the unit.

ALARM 38, Internal fault
When an internal fault occurs, a code number defined in
the table below is displayed.

Troubleshooting

Cycle power

Check that the option is properly installed

Check for loose or missing wiring

It may be necessary to contact your GE supplier or service
department. Note the code number for further trouble-
shooting directions.

No.

Text

0

Serial port cannot be initialised. Contact yourGE

supplier or GEService Department.

256-258

Power EEPROM data is defect or too old

512-519

Internal fault. Contact yourGE supplier or GE

Service Department.

783

Parameter value outside of min/max limits

1024-1284

Internal fault. Contact your GE supplier or the GE

Service Department.

1299

Option SW in slot A is too old

1300

Option SW in slot B is too old

1302

Option SW in slot C1 is too old

1315

Option SW in slot A is not supported (not allowed)

1316

Option SW in slot B is not supported (not allowed)

1318

Option SW in slot C1 is not supported (not

allowed)

1379-2819

Internal fault. Contact yourGE supplier or GEService

Department.

2820

keypad stack overflow

2821

Serial port overflow

2822

USB port overflow

3072-5122

Parameter value is outside its limits

5123

Option in slot A: Hardware incompatible with

control board hardware

5124

Option in slot B: Hardware incompatible with

control board hardware

5125

Option in slot C0: Hardware incompatible with

control board hardware

5126

Option in slot C1: Hardware incompatible with

control board hardware

5376-6231

Internal fault. Contact yourGE supplier or GEService

Department.

ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.

The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.

Warnings and Alarms

AF-600 FP Operating Instructions

54