Illustration 2.18 Location of Terminals 53 and 54 Switches

2.4.6 Serial Communication

Connect RS-485 serial communication wiring to terminals
(+)68 and (-)69.

Screened serial communication cable is
recommended

See 2.4.2 Earth (Grounding) Requirements for
proper grounding

Illustration 2.19 Serial Communication Wiring Diagram

For basic serial communication set-up, select the following

1.

Protocol type in O-30 Protocol.

2.

Drive address in O-31 Address.

3.

Baud rate in O-32 Drive Port Baud Rate.

Four communication protocols are internal to the
drive. Follow motor manufacturer wiring
requirements.

Drive profile

Modbus RTU

Metasys N2

®

Apogee FLN

®

Functions can be programmed remotely using
the protocol software and RS-485 connection or
in parameter group O-## Options / Comms

Selecting a specific communication protocol
changes various default parameter settings to
match that protocol’s specifications along with
making additional protocol-specific parameters
available

Option cards which install into the drive are
available to provide additional communication
protocols. See the option-card documentation for
installation and operation instructions

Installation

AF-600 FP Operating Instructions

18