1 purpose of the manual, 2 additional resources, 3 product overview – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 9: 4 internal drive controller functions

Advertising
background image

1.1 Purpose of the Manual

This manual is intended to provide detailed information for
the installation and start up of the frequency converter.
Chapter 2 Installation provides requirements for
mechanical and electrical installation, including input,
motor, control and serial communications wiring, and
control terminal functions. Chapter 3 Start Up and
Functional Testing
provides detailed procedures for start
up, basic operational programming, and functional testing.
The remaining chapters provide supplementary details.
These include user interface, detailed programming,
application examples, start-up troubleshooting, and specifi-
cations.

1.2 Additional

Resources

Other resources are available to understand advanced
drive functions and programming.

The Programming Guide provides greater detail
in how to work with parameters and many
application examples.

The Design Guide is intended to provide detailed
capabilities and functionality to design motor
control systems.

Optional equipment is available that may change
some of the procedures described. Be sure to see
the instructions supplied with those options for
specific requirements.

1.3 Product

Overview

A drive is an electronic motor controller that converts AC
mains input into a variable AC waveform output. The
frequency and voltage of the output are regulated to
control the motor speed or torque. The drive can vary the
speed of the motor in response to system feedback, such
as changing temperature or pressure for controlling fan,
compressor, or pump motors. The drive can also regulate
the motor by responding to remote commands from
external controllers.

In addition, the drive monitors the system and motor
status, issues warnings or alarms for fault conditions, starts
and stops the motor, optimizes energy efficiency, and
offers many more control, monitoring, and efficiency
functions. Operation and monitoring functions are
available as status indications to an outside control system
or serial communication network.

1.4 Internal Drive Controller Functions

Below is a block diagram of the frequency converter's
internal components. See Table 1.1 for their functions.

Illustration 1.3 Drive Block Diagram

Area

Title

Functions

1

Mains input

Three-phase AC mains power

supply to the drive

2

Rectifier

The rectifier bridge converts

the AC input to DC current to

supply inverter power

3

DC bus

The frequency converter's

intermediate DC-bus circuit

handles the DC current

4

DC reactors

Filter the intermediate DC

circuit voltage

Prove line transient protection

Reduce RMS current

Raise the power factor

reflected back to the line

Reduce harmonics on the AC

input

5

Capacitor bank

Stores the DC power

Provides ride-through

protection for short power

losses

6

Inverter

Converts the DC into a

controlled PWM AC waveform

for a controlled variable

output to the motor

7

Output to motor

Regulated three-phase output

power to the motor

8

Control circuitry

Input power, internal

processing, output, and motor

current are monitored to

provide efficient operation

and control

User interface and external

commands are monitored and

performed

Status output and control can

be provided

Table 1.1 Drive Internal Components

Introduction

AF-600 FP Operating Instructions

6

1

1

Advertising