6 application set-up examples, 1 introduction, 2 application examples – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual
Page 44
6 Application Set-Up Examples
6.1 Introduction
The examples in this section are intended as a quick
reference for common applications.
•
Parameter settings are the regional default values
unless otherwise indicated (selected in
K-03 Regional Settings)
•
Parameters associated with the terminals and
their settings are shown next to the drawings
•
Where switch settings for analog terminals A53 or
A54 are required, these are also shown
6.2 Application
Examples
Parameters
Function
Setting
AN-22 Terminal 54
Low Current
4mA*
AN-23 Terminal 54
High Current
20mA*
AN-24 Terminal 54
Low Ref./Feedb. Value
0*
AN-25 Terminal 54
High Ref./Feedb. Value
50*
* = Default Value
Notes/comments:
Table 6.1 Analog Current Feedback Transducer
Parameters
Function
Setting
AN-20 Terminal
54 Low Voltage
0.07V*
AN-21 Terminal
54 High Voltage
10V*
AN-24 Terminal
54 Low Ref./
Feedb. Value
0*
AN-25 Terminal
54 High Ref./
Feedb. Value
50*
* = Default Value
Notes/comments:
Table 6.2 Analog Voltage Feedback Transducer (3-wire)
Parameters
Function
Setting
AN-20 Terminal
54 Low Voltage
0.07V*
AN-21 Terminal
54 High Voltage
10V*
AN-24 Terminal
54 Low Ref./
Feedb. Value
0*
AN-25 Terminal
54 High Ref./
Feedb. Value
50*
* = Default Value
Notes/comments:
Table 6.3 Analog Voltage Feedback Transducer (4-wire)
Application Set-Up Examples
AF-600 FP Operating Instructions
41
6
6