GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 61

Advertising
background image

Symptom

Possible Cause

Test

Solution

Motor running in wrong

direction

Motor rotation limit

Check that H-08 Reverse Lock is

programmed correctly.

Program correct settings.

Active reversing signal

Check if a reversing command is

programmed for the terminal in

parameter group E-0# Digital inputs.

Deactivate reversing signal.

Wrong motor phase connection

See 3.5 Check Motor Rotation in this

manual.

Motor is not reaching

maximum speed

Frequency limits set wrong

Check output limits in F-17 Motor

Speed High Limit [RPM], F-15 Motor

Speed High Limit [Hz] and F-03 Max

Output Frequency 1

Program correct limits.

Reference input signal not scaled

correctly

Check reference input signal

scaling in AN-## reference limits in

parameter group F-5# Extended

Reference.

Program correct settings.

Motor speed unstable

Possible incorrect parameter

settings

Check the settings of all motor

parameters, including all motor

compensation settings. For closed

loop operation, check PID settings.

Check settings in parameter group

AN-##. For closed loop operation

check settings in parameter group

CL-0#

Motor runs rough

Possible over-magnetization

Check for incorrect motor settings

in all motor parameters.

Check motor settings in parameter

groups P-0# Motor Data, P-3# Adv

Motor Data, and H-5# Load Indep.

Setting.

Motor will not brake

Possible incorrect settings in the

brake parameters. Possible too

short ramp down times.

Check brake parameters. Check

ramp time settings.

Check parameter groupB-0# DC

brake and F-5# Extended Reference.

Open power fuses or circuit

breaker trip

Phase to phase short

Motor or panel has a short phase

to phase. Check motor and panel

phase to for shorts.

Eliminate any shorts detected.

Motor overload

Motor is overloaded for the

application.

Perform startup test and verify

motor current is within specifi-

cations. If motor current is

exceeding nameplate full load

current, motor may run only with

reduced load. Review the specifi-

cations for the application.

Loose connections

Perform pre-startup check for loose

connections.

Tighten loose connections.

Mains current imbalance

greater than 3%

Problem with mains power (See

Alarm 4 Mains phase loss

description)

Rotate input power leads into the

drive one position: A to B, B to C, C

to A.

If imbalanced leg follows the wire,

it is a power problem. Check mains

power supply.

Problem with the drive unit

Rotate input power leads into the

drive one position: A to B, B to C, C

to A.

If imbalance leg stays on same

input terminal, it is a problem with

the unit. Contact supplier.

Motor current imbalance

greater than 3%

Problem with motor or motor

wiring

Rotate output motor leads one

position: U to V, V to W, W to U.

If imbalanced leg follows the wire,

the problem is in the motor or

motor wiring. Check motor and

motor wiring.

Problem with drive unit

Rotate output motor leads one

position: U to V, V to W, W to U.

If imbalance leg stays on same

output terminal, it is a problem

with the unit. Contact supplier.

Basic Troubleshooting

AF-600 FP Operating Instructions

58