1 fault messages – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 54

Advertising
background image

No.

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter Reference

50

Auto Tune calibration failed

X

51

Auto Tune check U

nom

and I

nom

X

52

Auto Tune low I

nom

X

53

Auto Tune motor too big

X

54

Auto Tune motor too small

X

55

Auto Tune Parameter out of range

X

56

Auto Tune interrupted by user

X

57

Auto Tune timeout

X

58

Auto Tune internal fault

X

X

59

Current limit

X

60

External Interlock

X

62

Output Frequency at Maximum Limit

X

64

Voltage Limit

X

65

Control Board Over-temperature

X

X

X

66

Heat sink Temperature Low

X

67

Option Configuration has Changed

X

69

Pwr. Card Temp

X

X

70

Illegal Drive configuration

X

76

Power Unit Setup

X

79

Illegal PS config

X

X

80

Drive Initialized to Default Value

X

91

Analog input 54 wrong settings

X

92

NoFlow

X

X

AP-2#

93

Dry Pump

X

X

AP-2#

94

End of Curve

X

X

AP-5#

95

Broken Belt

X

X

AP-6#

96

Start Delayed

X

AP-7#

97

Stop Delayed

X

AP-7#

98

Clock Fault

X

K-7#

201

Fire M was Active

202

Fire M Limits Exceeded

203

Missing Motor

204

Locked Rotor

243

Brake IGBT

X

X

244

Heatsink temp

X

X

X

245

Heatsink sensor

X

X

246

Pwr.card supply

X

X

247

Pwr.card temp

X

X

248

Illegal PS config

X

X

250

New spare parts

X

251

New Type Code

X

X

Table 8.1 Alarm/Warning code list

(X) Dependent on parameter

1)

Cannot be Auto reset via H-04 Auto-Reset (Times)

8.4.1 Fault Messages

The warning/alarm information below defines the warning/
alarm condition, provides the probable cause for the
condition, and details a remedy or troubleshooting
procedure.

WARNING 1, 10 Volts low
The control card voltage is below 10 V from terminal 50.

Remove some of the load from terminal 50, as the 10 V
supply is overloaded. Max. 15 mA or minimum 590

Ω.

This condition can be caused by a short in a connected
potentiometer or improper wiring of the potentiometer.

Troubleshooting: Remove the wiring from terminal 50. If
the warning clears, the problem is with the customer
wiring. If the warning does not clear, replace the control
card.