Caution – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 47

Advertising
background image

will always be the set-up that is edited. If you
prefer you can also ignore this and manually
control what set-up you want to edit through
par. K-11.

4.

Set par. E-03 Terminal 27 Digital Input to [23] Set-
up select bit 0. When terminal 27 is OFF, set-up 1
(hand) is active, when it is ON, set-up 2 (auto) is
active.

5.

Set par. F-01 Frequency Setting 1 to Analog input
53 (hand mode).

6.

Copy set-up 1 to set-up 2. Set par. K-51 Set up
Copy to [2] Copy to set-up 2. Now setup 1 and 2
are identical.

7.

If you need to be able to change between hand
and auto mode while the motor is running you
will have to link the 2 set-ups together. Set par.
K-12 This Set-up Linked to to [2] set-up 2.

8.

Change to set-up 2 by setting input 27 ON (if par.
K-11 is [9]) or by setting par. K-11 Edit Set-up to
set-up 2.

9.

Set par. F-01 Frequency Setting 1 to Analog input
54 (auto mode). If you want different settings in
hand and auto mode, like different accel/decel
ramps, speed limits etc. you can now programme
them. You just have to make sure you edit the
correct set-up. Set-up 1 is Hand mode and set-up
2 is Auto mode.

Parameters

Function

Setting

E-01 Terminal 18

Digital Input

[8] Start*

E-03 Terminal 27

Digital Input

[23[ Set-up

select bit 0

* = Default Value

Notes/comments:

GE 30mm HOA Cat# (1)

104PSG34B & (3) CR104PXC1

Table 6.11 HOA

Parameters

Function

Setting

O-30 Protocol

Drive*

O-31 Address

1*

O-32 Drive Port

Baud Rate

9600*

* = Default Value

Notes/comments:

Select protocol, address and

baud rate in the above

mentioned parameters.

Table 6.12 RS-485 Network Connection (N2, FLN, Modbus RTU, Drive)

CAUTION

Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.

Application Set-Up Examples

AF-600 FP Operating Instructions