Caution – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 72

Advertising
background image

Surroundings:
Unit Size 1x types

IP 20/Chassis, IP 21kit/Type 1, IP55/Type12

Unit Size 21 and 22 types

IP55/Type12

Unit Size 23 and 24 types

IP20/Chassis

Unit Size 31 and 32 types

IP55/Type 12

Unit Size 33 and 34 types

IP20/Chassis

Unit Size 41, 42, and 51 types

IP21/Type 1, IP54/Type12

Unit Size 43, 44, and 52 types

IP00/Chassis

Unit Size 61/63

IP21, 54/Type1, 12

Unit Size 62/64

IP21, 54/Type1, 12

IP21/Nema 1 kit for all unit sizes 1x, 2x, and 3x

IP21/NEMA 1/on top of enclosure

Vibration test all enclosure types

1.0g

Relative humidity

5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation

Aggressive environment (IEC 60068-2-43) H

2

S test

class Kd

Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)

- with derating

max. 50

°C

1)

- with full output power of typical EFF2 motors (up to 90% output current)

max. 50

°C

1)

- at full continuous Drive output current

max. 45

°C

1)

1)

For more information on derating see the AF-600 FP Design Guide, section on Special Conditions.

Minimum ambient temperature during full-scale operation

0

°C

Minimum ambient temperature at reduced performance

- 10

°C

Temperature during storage/transport

-25 - +65/70

°°C

Maximum altitude above sea level without derating

1000m

Maximum altitude above sea level with derating

3000m

Derating for high altitude, see section on special conditions

EMC standards, Emission

EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3

EMC standards, Immunity

EN 61800-3, EN 61000-6-1/2,

EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6

See section on special conditions!

Control card performance:
Scan interval

5 ms

Control card, USB Serial Communication:
USB standard

1.1 (Full speed)

USB plug

USB type B “device” plug

CAUTION

Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from protection earth. Use only isolated laptop/PC as connection to the USB
connector on drive or an isolated USB cable/converter.

Specifications

AF-600 FP Operating Instructions

69

10

10

Advertising