GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 70

Advertising
background image

Analog inputs:
Number of analog inputs

2

Terminal number

53, 54

Modes

Voltage or current

Mode select

Switches A53 and A54

Voltage mode

Switch A53/A54 = (U)

Voltage level

0 to + 10V (scaleable)

Input resistance, R

i

approx. 10 k

Max. voltage

± 20 V

Current mode

Switch A53/A54 = (I)

Current level

0/4 to 20 mA (scaleable)

Input resistance, R

i

approx. 200

Max. current

30 mA

Resolution for analog inputs

10 bit (+ sign)

Accuracy of analog inputs

Max. error 0.5% of full scale

Bandwidth

200Hz

The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

Pulse inputs:
Programmable pulse inputs

2

Terminal number pulse

29, 33

Max. frequency at terminal, 29, 33

110 kHz (Push-pull driven)

Max. frequency at terminal, 29, 33

5 kHz (open collector)

Min. frequency at terminal 29, 33

4 Hz

Voltage level

see section on Digital input

Maximum voltage on input

28 V DC

Input resistance, R

i

approx. 4 k

Pulse input accuracy (0.1 - 1 kHz)

Max. error: 0.1% of full scale

Analog output:
Number of programmable analog outputs

1

Terminal number

42

Current range at analog output

0/4 - 20 mA

Max. resistor load to common at analog output

500

Accuracy on analog output

Max. error: 0.8 % of full scale

Resolution on analog output

8 bit

The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

Control card, RS-485 serial communication:
Terminal number

68 (P,TX+, RX+), 69 (N,TX-, RX-)

Terminal number 61

Common for terminals 68 and 69

The RS-485 serial communication circuit is functionally seated from other central circuits and galvanically isolated from the
supply voltage (PELV).

Specifications

AF-600 FP Operating Instructions

67