Operation

Status

DC Hold

DC hold is selected in H-80 Function at Stop

and a stop command is active. The motor is

held by a DC current set in B-00 DC Hold

Current.

DC Stop

The motor is held with a DC current (B-01 DC

Brake Current) for a specified time (B-02 DC

Braking Time).

DC Brake is activated in B-03 DC Brake Cut

In Speed [RPM] and a Stop command is

active.

DC Brake (inverse) is selected as a function

for a digital input. The corresponding

terminal is not active.

The DC Brake is activated via serial

communication.

Feedback high

The sum of all active feedbacks is above the

feedback limit set in H-77 Warning Feedback

High.

Feedback low

The sum of all active feedbacks is below the

feedback limit set in H-76 Warning Feedback

Low.

Freeze output

The remote reference is active which holds

the present speed.

Freeze output was selected as a function

for a digital input. The corresponding

terminal is active. Speed control is only

possible via the terminal functions speed

up and speed down.

Hold ramp is activated via serial communi-

cation.

Freeze output

request

A freeze output command has been given,

but the motor will remain stopped until a run

permissive signal is received.

Freeze ref.

Freeze Reference was chosen as a function for

a digital input. The corresponding terminal is

active. The drive saves the actual reference.

Changing the reference is now only possible

via terminal functions speed up and speed

down.

Jog request

A jog command has been given, but the

motor will be stopped until a run permissive

signal is received via a digital input.

Jogging

The motor is running as programmed in

C-21 Jog Speed [RPM].

Jog was selected as function for a digital

input. The corresponding terminal (e.g.

Terminal 29) is active.

The Jog function is activated via the serial

communication.

The Jog function was selected as a

reaction for a monitoring function (e.g. No

signal). The monitoring function is active.

Operation

Status

OVC control

Overvoltage control was activated in B-17 Over-

voltage Control. The connected motor is

supplying the drive with generative energy.

The overvoltage control adjusts the V/Hz ratio

to run the motor in controlled mode and to

prevent the drive from tripping.

PowerUnit Off

(For frequency converters with an external 24V

power supply installed only.) Mains supply to

the drive is removed, but the control card is

supplied by the external 24V.

Protection md

Protection mode is active. The unit has

detected a critical status (an overcurrent or

overvoltage).

To avoid tripping, switching frequency is

reduced to 4kHz.

If possible, protection mode ends after

approximately 10sec.

Protection mode can be restricted in

SP-26 Trip Delay at Drive Fault

QStop

The motor is decelerating using C-23 Quick

Stop Decel Time.

Quick stop inverse was chosen as a function

for a digital input. The corresponding

terminal is not active.

The quick stop function was activated via

serial communication.

Ramping

The motor is accelerating/decelerating using

the active Ramp Up/Down. The reference, a

limit value or a standstill is not yet reached.

Ref. high

The sum of all active references is above the

reference limit set in H-75 Warning Reference

High.

Ref. low

The sum of all active references is below the

reference limit set in H-74 Warning Reference

Low .

Run on ref.

The drive is running in the reference range.

The feedback value matches the setpoint

value.

Run request

A start command has been given, but the

motor is stopped until a run permissive signal

is received via digital input.

Running

The motor is driven by the drive.

Sleep Mode

The energy saving function is enabled. This

means that at present the motor has stopped,

but that it will restart automatically when

required.

Speed high

Motor speed is above the value set in

H-73 Warning Speed High.

Speed low

Motor speed is below the value set in

H-72 Warning Speed Low.

Standby

In Auto mode, the drive will start the motor

with a start signal from a digital input or serial

communication.

Status Messages

AF-600 FP Operating Instructions

47