4 warning and alarm definitions – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 53

Advertising
background image

8.4 Warning and Alarm Definitions

Table 8.1 defines whether a warning is issued prior to an alarm, and whether the alarm trips the unit or trip locks the unit.

No.

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter Reference

1

10 Volts low

X

2

Live zero error

(X)

(X)

AN-01 Live Zero Timeout

Function

4

Mains phase loss

(X)

(X)

(X)

SP-12 Function at Line

Imbalance

5

DC link voltage high

X

6

DC link voltage low

X

7

DC over voltage

X

X

8

DC under voltage

X

X

9

Inverter overloaded

X

X

10

Motor Electronic Thermal Overload over

temperature

(X)

(X)

F-10 Electronic Overload

11

Motor thermistor over temperature

(X)

(X)

F-10 Electronic Overload

12

Torque limit

X

X

13

Over Current

X

X

X

14

Earth fault

X

X

X

15

Hardware mismatch

X

X

16

Short Circuit

X

X

17

Control word timeout

(X)

(X)

O-04 Control Word

Timeout Function

18

Start Failed

23

Internal Fan Fault

X

24

External Fan Fault

X

SP-53 Fan Monitor

29

Drive over temperature

X

X

X

30

Motor phase U missing

(X)

(X)

(X)

H-78 Missing Motor Phase

Function

31

Motor phase V missing

(X)

(X)

(X)

H-78 Missing Motor Phase

Function

32

Motor phase W missing

(X)

(X)

(X)

H-78 Missing Motor Phase

Function

33

Inrush fault

X

X

34

Fieldbus communication fault

X

X

35

Option Fault

X

X

36

Mains failure

X

X

38

Internal fault

X

X

39

Heatsink sensor

X

X

40

Overload of Digital Output Terminal 27

(X)

E-00 Digital I/O Mode,

E-51 Terminal 27 Mode

41

Overload of Digital Output Terminal 29

(X)

E-00 Digital I/O Mode,

E-52 Terminal 29 Mode

42

Overload of Digital Output On X30/6

(X)

E-56 Term X30/6 Digi Out

(OPCGPIO)

42

Overload of Digital Output On X30/7

(X)

E-57 Term X30/7 Digi Out

(OPCGPIO)

45

45 Earth Fault 2

46

Pwr. card supply

X

X

47

24V supply low

X

X

X

48

1.8V supply low

X

X

49

Speed limit

X

(X)

H-36 Trip Speed Low [RPM]

Warnings and Alarms

AF-600 FP Operating Instructions

50

8

8

Advertising