4 warning and alarm definitions – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual
Page 53
8.4 Warning and Alarm Definitions
Table 8.1 defines whether a warning is issued prior to an alarm, and whether the alarm trips the unit or trip locks the unit.
No.
Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter Reference
1
10 Volts low
X
2
Live zero error
(X)
(X)
AN-01 Live Zero Timeout
Function
4
Mains phase loss
(X)
(X)
(X)
SP-12 Function at Line
Imbalance
5
DC link voltage high
X
6
DC link voltage low
X
7
DC over voltage
X
X
8
DC under voltage
X
X
9
Inverter overloaded
X
X
10
Motor Electronic Thermal Overload over
temperature
(X)
(X)
F-10 Electronic Overload
11
Motor thermistor over temperature
(X)
(X)
F-10 Electronic Overload
12
Torque limit
X
X
13
Over Current
X
X
X
14
Earth fault
X
X
X
15
Hardware mismatch
X
X
16
Short Circuit
X
X
17
Control word timeout
(X)
(X)
O-04 Control Word
Timeout Function
18
Start Failed
23
Internal Fan Fault
X
24
External Fan Fault
X
SP-53 Fan Monitor
29
Drive over temperature
X
X
X
30
Motor phase U missing
(X)
(X)
(X)
H-78 Missing Motor Phase
Function
31
Motor phase V missing
(X)
(X)
(X)
H-78 Missing Motor Phase
Function
32
Motor phase W missing
(X)
(X)
(X)
H-78 Missing Motor Phase
Function
33
Inrush fault
X
X
34
Fieldbus communication fault
X
X
35
Option Fault
X
X
36
Mains failure
X
X
38
Internal fault
X
X
39
Heatsink sensor
X
X
40
Overload of Digital Output Terminal 27
(X)
E-00 Digital I/O Mode,
E-51 Terminal 27 Mode
41
Overload of Digital Output Terminal 29
(X)
E-00 Digital I/O Mode,
E-52 Terminal 29 Mode
42
Overload of Digital Output On X30/6
(X)
E-56 Term X30/6 Digi Out
(OPCGPIO)
42
Overload of Digital Output On X30/7
(X)
E-57 Term X30/7 Digi Out
(OPCGPIO)
45
45 Earth Fault 2
46
Pwr. card supply
X
X
47
24V supply low
X
X
X
48
1.8V supply low
X
X
49
Speed limit
X
(X)
H-36 Trip Speed Low [RPM]
Warnings and Alarms
AF-600 FP Operating Instructions
50
8
8