10.2 General Technical Data

Mains supply (L1, L2, L3):

Supply voltage

200-240V

±10%, 380-480V ±10%, 525-600V ±10%,

Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque
cannot be expected at mains voltage lower than 10% below the drive's lowest rated supply voltage.

Supply frequency

50/60Hz

±5%

Max. imbalance temporary between mains phases

3.0% of rated supply voltage

True Power Factor ()

≥ 0.9 nominal at rated load

Displacement Power Factor (cos) near unity

(> 0.98)

Switching on input supply L1, L2, L3 (power-ups)

≤ unit size 1x

maximum twice/min.

Switching on input supply L1, L2, L3 (power-ups)

≥ unit sizes 2x, 3x

maximum once/min.

Switching on input supply L1, L2, L3 (power-ups)

≥ unit sizes 4x, 5x, 6x

maximum once/2 min.

Environment according to EN60664-1

overvoltage category III / pollution degree 2

The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/600 V
maximum.

Motor output (U, V, W):
Output voltage

0 - 100% of supply voltage

Output frequency

0 - 1000 Hz

*

Switching on output

Unlimited

Accel/Decel Times

1 - 3600 sec.

*

Dependent on power size.

Torque characteristics:

Starting torque (Constant torque)

maximum 110% for 1 min.

*

Starting torque

maximum 135% up to 0.5 sec.

*

Overload torque (Constant torque)

maximum 110% for 1 min.

*

*Percentage relates to the frequency converter's nominal torque.

Cable lengths and cross sections:
Max. motor cable length, screened/armoured

150 m

Max. motor cable length, unscreened/unarmoured

300 m

Max. cross section to motorand mains*

Maximum cross section to control terminals, rigid wire

1.5 mm

2

/16 AWG (2 x 0.75 mm

2

)

Maximum cross section to control terminals, flexible cable

1 mm

2

/18 AWG

Maximum cross section to control terminals, cable with enclosed core

0.5 mm

2

/20 AWG

Minimum cross section to control terminals

0.25 mm

2

* See 10.1 Power-dependent Specifications for more information!

Digital inputs:
Programmable digital inputs

4 (6)

Terminal number

18, 19, 27

1)

, 29, 32, 33,

Logic

PNP or NPN

Voltage level

0 - 24V DC

Voltage level, logic'0' PNP

< 5V DC

Voltage level, logic'1' PNP

> 10V DC

Voltage level, logic '0' NPN

> 19 V DC

Voltage level, logic '1' NPN

< 14V DC

Maximum voltage on input

28V DC

Input resistance, R

i

approx. 4k

All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.

Specifications

AF-600 FP Operating Instructions

66

10