GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 71

Advertising
background image

Digital output:
Programmable digital/pulse outputs

2

Terminal number

27, 29

1)

Voltage level at digital/frequency output

0 - 24 V

Max. output current (sink or source)

40 mA

Max. load at frequency output

1 k

Max. capacitive load at frequency output

10 nF

Minimum output frequency at frequency output

0 Hz

Maximum output frequency at frequency output

32 kHz

Accuracy of frequency output

Max. error: 0.1 % of full scale

Resolution of frequency outputs

12 bit

1) Terminal 27 and 29 can also be programmed as input.

The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

Control card, 24 V DC output:
Terminal number

12, 13

Max. load

200mA

The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.

Relay outputs:
Programmable relay outputs

2

Relay 01 Terminal number

1-3 (break), 1-2 (make)

Max. terminal load (AC-1)

1)

on 1-3 (NC), 1-2 (NO) (Resistive load)

240V AC, 2A

Max. terminal load (AC-15)

1)

(Inductive load

@ cosφ 0.4)

240V AC, 0.2A

Max. terminal load (DC-1)

1)

on 1-2 (NO), 1-3 (NC) (Resistive load)

60V DC, 1A

Max. terminal load (DC-13)

1)

(Inductive load)

24V DC, 0.1A

Relay 02 Terminal number

4-6 (break), 4-5 (make)

Max. terminal load (AC-1)

1)

on 4-5 (NO) (Resistive load)

2)3)

400V AC, 2A

Max. terminal load (AC-15)

1)

on 4-5 (NO) (Inductive load

@ cosφ 0.4)

240V AC, 0.2A

Max. terminal load (DC-1)

1)

on 4-5 (NO) (Resistive load)

80V DC, 2A

Max. terminal load (DC-13)

1)

on 4-5 (NO) (Inductive load)

24V DC, 0.1A

Max. terminal load (AC-1)

1)

on 4-6 (NC) (Resistive load)

240V AC, 2A

Max. terminal load (AC-15)

1)

on 4-6 (NC) (Inductive load

@ cosφ 0.4)

240V AC, 0.2A

Max. terminal load (DC-1)

1)

on 4-6 (NC) (Resistive load)

50V DC, 2A

Max. terminal load (DC-13)

1)

on 4-6 (NC) (Inductive load)

24V DC, 0.1A

Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)

24V DC 10mA, 24V AC 2 mA

Environment according to EN 60664-1

overvoltage category III/pollution degree 2

1) IEC 60947 t 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300V AC 2A

Control card, 10 V DC output:
Terminal number

50

Output voltage

10.5 V

±0.5 V

Max. load

25 mA

The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

Control characteristics:
Resolution of output frequency at 0 - 1000 Hz

+/- 0.003 Hz

System response time (terminals 18, 19, 27, 29, 32, 33)

≤ 2 ms

Speed control range (open loop)

1:100 of synchronous speed

Speed accuracy (open loop)

30 - 4000 rpm: Maximum error of

±8 rpm

All control characteristics are based on a 4-pole asynchronous motor

Specifications

AF-600 FP Operating Instructions

68

10

0

Advertising