2 ce compliance – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 75

Advertising
background image

10.3.2 CE Compliance

Fuses or Circuit Breakers are mandatory to comply with IEC 60364. GE recommend using a selection of the following.

The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V,
or 600V depending on the drive voltage rating. With the proper fusing the drive short circuit current rating (SCCR) is
100,000 Arms.

AF-600 3-phase

Recommended fuse size

Recommended max fuse

Recommended circuit breaker

Max trip level

[HP]

[A]

1

gG-16

gG-25

PKZM0-25

25

2

3

5

gG-20

gG-32

7,5

gG-50

gG-63

PKZM4-50

50

10

15

20

gG-80

gG-125

NZMB1-A100

100

25

30

gG-125

gG-150

NZMB2-A200

150

40

aR-160

aR-160

50

aR-200

aR-200

NZMB2-A250

250

60

aR-250

aR-250

Table 10.7 200-240V, IP20/Open Chassis

AF-600 3-phase

Recommended fuse size

Recommended max fuse

Recommended circuit breaker

Max trip level

[HP]

[A]

1

gG-20

gG-32

PKZM0-25

25

2

3

5

7,5

gG-63

gG-80

PKZM4-63

63

10

15

20

gG-80

gG-100

NZMB1-A100

100

25

gG-125

gG-160

NZMB2-A200

160

30

40

aR-160

aR-160

50

aR-200

aR-200

NZMB2-A250

250

60

aR-250

aR-250

Table 10.8 200-240V, IP55/Nema 12