istics with the data entered in P-02, P-03, P-06,
P-07, F-04 and F-05.

It does not cause the motor to run or harm to
the motor

Some motors may be unable to run the complete
version of the test. In that case, select Reduced
Auto Tune

If an output filter is connected to the motor,
select Reduced Auto Tune

If warnings or alarms occur, see 8 Warnings and
Alarms

Run this procedure on a cold motor for best
results

3.5 Check

Motor

Rotation

Prior to running the drive, check the motor rotation. The
motor will run briefly at 5Hz or the minimum frequency set
in F-16 Motor Speed Low Limit [Hz].

1.

Press [Main Menu] twice on the keypad.

2.

Enter Parameter Data Set and scroll to P-## Motor
Data and press [OK] to enter.

3.

Scroll to P-08 Motor Rotation Check.

4.

Press [OK].

5.

Scroll to Enable.

The following text will appear: Note! Motor may run in
wrong direction
.

6.

Press [OK].

7.

Follow the on-screen instructions.

To change the direction of rotation, remove power to the
drive and wait for power to discharge. Reverse the
connection of any two of the three motor cables on the
motor or drive side of the connection.

3.6 Local-control

Test

CAUTION

MOTOR START!

Ensure that the motor, system, and any attached
equipment is ready for start. It is the responsibility of the
user to ensure safe operation under any operational
condition. Failure to ensure that the motor, system, and
any attached equipment is ready for start could result in
personal injury or equipment damage.

NOTE

The hand key on the keypad provides a local start
command to the drive. The OFF key provides the stop
function.
When operating in local mode, the up and down arrows
on the keypad increase and decrease the speed output of
the drive. The left and right arrow keys move the display
cursor in the numeric display.

1.

Press [Hand].

2.

Accelerate the drive by pressing [

] to full speed.

Moving the cursor left of the decimal point
provides quicker input changes.

3.

Note any acceleration problems.

4.

Press [OFF].

5.

Note any deceleration problems.

If acceleration problems were encountered

If warnings or alarms occur, see 8 Warnings and
Alarms

Check that motor data is entered correctly

Increase the accel time in F-07 Accel Time 1

Increase current limit in F-43 Current Limit

Increase torque limit in F-40 Torque Limiter
(Driving)

If deceleration problems were encountered

If warnings or alarms occur, see 8 Warnings and
Alarms

Check that motor data is entered correctly

Increase the decel time in F-08 Decel Time 1

See 8.4 Warning and Alarm Definitions for resetting the
drive after a trip.

NOTE

3.1 Pre-start through 3.6 Local-control Test in this chapter
concludes the procedures for applying power to the drive,
basic programming, set-up, and functional testing.

Start Up and Functional Tes...

AF-600 FP Operating Instructions

22

3