GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 81

Advertising
background image

Recommended max. fuse

AF-600 1-

phase

AF-600 3-

phase

Bussmann

Littel fuse

Ferraz-

Shawmut

Ferraz-

Shawmut

HP

HP

Type JFHR2

2)

Type JFHR2

Type JFHR2

4)

Type J

1

FWX-10

-

-

HSJ-10

2

FWX-15

-

-

HSJ-15

2

3

FWX-20

-

-

HSJ-20

3

5

FWX-30

-

-

HSJ-30

5

7.5-10

FWX-50

-

-

HSJ-50

7.5

15

FWX-60

-

-

HSJ-60

10

20

FWX-80

-

-

HSJ-80

25-30

FWX-125

-

-

HSJ-125

20

40

FWX-150

L25S-150

A25X-150

HSJ-150

30

50

FWX-200

L25S-200

A25X-200

HSJ-200

60

FWX-250

L25S-250

A25X-250

HSJ-250

Table 10.15 200-240V

1) KTS-fuses from Bussmann may substitute KTN for 240V frequency converters.

2) FWH-fuses from Bussmann may substitute FWX for 240V frequency converters.

3) A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240V frequency converters.

4) A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240V frequency converters.

Recommended max. fuse

AF-600

1-phase

AF-600

3-phase

Bussmann

Bussmann

Bussmann

Bussmann

Bussmann

Bussmann

[HP]

[HP]

Type RK1

Type J

Type T

Type CC

Type CC

Type CC

1

KTS-R-6

JKS-6

JJS-6

FNQ-R-6

KTK-R-6

LP-CC-6

2-3

KTS-R-10

JKS-10

JJS-10

FNQ-R-10

KTK-R-10

LP-CC-10

5

KTS-R-20

JKS-20

JJS-20

FNQ-R-20

KTK-R-20

LP-CC-20

7.5

KTS-R-25

JKS-25

JJS-25

FNQ-R-25

KTK-R-25

LP-CC-25

10

KTS-R-30

JKS-30

JJS-30

FNQ-R-30

KTK-R-30

LP-CC-30

15-20

KTS-R-40

JKS-40

JJS-40

-

-

-

25

KTS-R-50

JKS-50

JJS-50

-

-

-

10

30

KTS-R-60

JKS-60

JJS-60

-

-

-

15

40

KTS-R-80

JKS-80

JJS-80

-

-

-

50

KTS-R-100

JKS-100

JJS-100

-

-

-

60

KTS-R-125

JKS-125

JJS-125

-

-

-

25

75

KTS-R-150

JKS-150

JJS-150

-

-

-

50

100

KTS-R-200

JKS-200

JJS-200

-

-

-

125

KTS-R-250

JKS-250

JJS-250

-

-

-

Table 10.16 380-480V, 125HP and below