4 substitute fuses for 240 v, 4 connection tightening torques – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual
Page 86
10.3.4 Substitute Fuses for 240 V
Original fuse
Manufacturer
Substitute fuses
KTN
Bussmann
KTS
FWX
Bussmann
FWH
KLNR
LITTEL FUSE
KLSR
L50S
LITTEL FUSE
L50S
A2KR
FERRAZ SHAWMUT
A6KR
A25X
FERRAZ SHAWMUT
A50X
10.4 Connection Tightening Torques
Power (HP)
Torque (Nm)
Unit
200-240V
380-480V
525-600V
Mains
Motor
DC
connection
Brake
Earth
Relay
12
1-3
1-5
1-5
1.8
1.8
1.8
1.8
3
0.6
13
5
7.5-10
7.5-10
1.8
1.8
1.8
1.8
3
0.6
15
1-5
1-10
1-10
1.8
1.8
1.8
1.8
3
0.6
21
7.5-15
15-25
15-25
1.8
1.8
1.5
1.5
3
0.6
22
-
20
30
40
30
40
4.5
4.5
2)
4.5
4.5
2)
3.7
3.7
3.7
3.7
3
3
0.6
0.6
23
7.5-15
15-25
15-25
1.8
1.8
1.8
1.8
3
0.6
24
20-25
30-50
30-50
4.5
4.5
4.5
4.5
3
0.6
31
25-40
50-75
50-75
10
10
10
10
3
0.6
32
50-60
100-125
100-125
14/24
1)
14/24
1)
14
14
3
0.6
33
30-40
60-75
60-75
10
10
10
10
3
0.6
34
50-60
100-125
100-125
14/24
1)
14/24
1)
14
14
3
0.6
Table 10.25 Tightening of Terminals
1) For different cable dimensions x/y, where x
≤ 95mm
2
and y
≥ 95mm
2
.
2) Cable dimensions above 18.5kW
≥ 35mm
2
and below 22kW
≤ 10mm
2
.
Specifications
AF-600 FP Operating Instructions
83
10
10