10.3.4 Substitute Fuses for 240 V

Original fuse

Manufacturer

Substitute fuses

KTN

Bussmann

KTS

FWX

Bussmann

FWH

KLNR

LITTEL FUSE

KLSR

L50S

LITTEL FUSE

L50S

A2KR

FERRAZ SHAWMUT

A6KR

A25X

FERRAZ SHAWMUT

A50X

10.4 Connection Tightening Torques

Power (HP)

Torque (Nm)

Unit

200-240V

380-480V

525-600V

Mains

Motor

DC

connection

Brake

Earth

Relay

12

1-3

1-5

1-5

1.8

1.8

1.8

1.8

3

0.6

13

5

7.5-10

7.5-10

1.8

1.8

1.8

1.8

3

0.6

15

1-5

1-10

1-10

1.8

1.8

1.8

1.8

3

0.6

21

7.5-15

15-25

15-25

1.8

1.8

1.5

1.5

3

0.6

22

-

20

30

40

30

40

4.5

4.5

2)

4.5

4.5

2)

3.7

3.7

3.7

3.7

3

3

0.6

0.6

23

7.5-15

15-25

15-25

1.8

1.8

1.8

1.8

3

0.6

24

20-25

30-50

30-50

4.5

4.5

4.5

4.5

3

0.6

31

25-40

50-75

50-75

10

10

10

10

3

0.6

32

50-60

100-125

100-125

14/24

1)

14/24

1)

14

14

3

0.6

33

30-40

60-75

60-75

10

10

10

10

3

0.6

34

50-60

100-125

100-125

14/24

1)

14/24

1)

14

14

3

0.6

Table 10.25 Tightening of Terminals

1) For different cable dimensions x/y, where x

≤ 95mm

2

and y

≥ 95mm

2

.

2) Cable dimensions above 18.5kW

≥ 35mm

2

and below 22kW

≤ 10mm

2

.

Specifications

AF-600 FP Operating Instructions

83

10

10

Advertising