1 parameter data check – GE Industrial Solutions AF-600 FP Fan & Pump Drive (230V to 60HP, 460_575V to 125HP) User Manual

Page 34

Advertising
background image

2.

Scroll to parameter group E-## Digital In/Out and
press [OK].

3.

Scroll to parameter group E-0# Digital Inputs and
press [OK]

4.

Scroll to E-01 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
Start is shown.

5.4 International/North American Default

Parameter Settings

Setting K-03 Regional Settings to [0]International or [1]
North America changes the default settings for some
parameters. Table 5.1 lists those parameters that are
effected.

Parameter

International

Default Parameter

Value

North American

Default Parameter

Value

K-03 Regional

Settings

International

North America

K-71 Date Format

DD-MM-YYYY

MM/DD/YYYY

K-72 Time Format

24h

12h

P-07 Motor Power

[kW]

See Note 1

See Note 1

P-02 Motor Power

[HP]

See Note 2

See Note 2

F-05 Motor Rated

Voltage

230V/400V/575V

208V/460V/575V

Parameter

International

Default Parameter

Value

North American

Default Parameter

Value

F-04 Base

Frequency

50Hz

60Hz

F-53 Maximum

Reference

50Hz

60Hz

F-54 Reference

Function

Sum

External/Preset

F-17 Motor Speed

High Limit [RPM]

See Note 3

1500RPM

1800RPM

F-15 Motor Speed

High Limit [Hz]

See Note 4

50Hz

60Hz

F-03 Max Output

Frequency 1

100Hz

120Hz

H-73 Warning

Speed High

1500RPM

1800RPM

E-03 Terminal 27

Digital Input

Coast inverse

External interlock

E-24 Function Relay Alarm

No alarm

AN-15 Terminal 53

High Ref./Feedb.

Value

50

60

AN-50 Terminal 42

Output

Speed 0 - HighLim

Speed 4-20mA

H-04 Auto-Reset

(Times)

Manual reset

Infinite auto reset

AP-85 Speed at

Design Point [RPM]

See Note 3

1500RPM

1800RPM

AP-86 Speed at

Design Point [Hz]

50Hz

60Hz

FB-04 Fire Mode

Max Reference

50Hz

60Hz

Table 5.1 International/North American Default Parameter Settings

Note 1: P-07 Motor Power [kW] is only visible when
K-03 Regional Settings is set to [0] International.
Note 2: P-02 Motor Power [HP], is only visible when
K-03 Regional Settings is set to [1] North America.
Note 3: This parameter is only visible when K-02 Motor
Speed Unit
is set to [0] RPM.
Note 4: This parameter is only visible when K-02 Motor
Speed Unit
is set to [1] Hz.
Changes made to default settings are stored and available
for viewing in the quick menu along with any
programming entered into parameters.

5.4.1 Parameter Data Check

1.

Press [Quick Menu].

2.

Scroll to Q5 Changes Made and press [OK].

About Drive Programming

AF-600 FP Operating Instructions