Galaxy Power System Verification Procedures

4 - 2 Replacement Procedures

Issue 3 January 2008

Memory Backup Battery Replacement for SC/SCF Controller

Introduction

The memory backup battery is located on the BJH (Intelligent
Controller) circuit pack. The battery provides power to retain system
configuration stored in memory in the event the BJH circuit pack is
removed or input power to the Galaxy Controller is interrupted. Battery
life is usually about five years.

When the memory backup battery is low, the Memory Backup Battery
Low warning is active and the battery should be replaced. Perform the
following three procedures to replace the memory backup battery to
prevent loss of system configuration:

Backup System Configuration

Replace Memory Backup Battery

Restore System Configuration

Backup System

Configuration

Use the EasyView software to perform a backup of the system
configuration. Refer to the discussion of EasyView in the controller
product manual. (If you need to install EasyView for the first time, see
the Product Manual “EasyView Software for the Galaxy Controller,”
Select Code 193-104-105.) Follow these steps to perform the backup:

Step

Action

1

Log in and begin an EasyView session.

2

Open the File menu and select Backup. Select a filename
and directory to store the system configuration. Click OK.
EasyView displays the status of the backup. Click OK when
the Backup operation is completed.

3

Open the Options menu and select Setup Sites. Select your
connection profile from the Site list. Click Modify. Change
the Administrator password to the default password
“administrator.” Change the Connect password to
“administrator.” Click OK. Click Close.

4

Open the Connect menu and select Disconnect to end the
EasyView session.