Galaxy Power System Verification Procedures

4 - 10 Replacement Procedures

Issue 3 January 2008

GPS2424 Replacement Procedures

Installing or

Replacing a 596B3

Rectifier

Step

Action

1

Locate and turn off the ac service feeding the rectifier.

Note: Do not turn off ac service to the entire system, only to
the rectifier that has failed.

2

Turn the rectifier’s ON/STBY switch to STBY.

Caution

Rear portion of the rectifier or converter that is in
operation is HOT to the touch. Use appropriate
precautions.

3

(Steps 3 and 4 for replacement only. For a new installation,
proceed to Step 5.)

Locate the Allen-head bolt in the center of the rectifier front
panel. Using the Allen wrench provided, rotate the bolt
counterclockwise to release the rectifier for removal.

4

Caution

Handle the rectifier or converter using two hands, one
hand supporting the rear of the unit, the other hand on the
front handle.

Grasp the front handle and slide/pull the rectifier from the
shelf assembly. Support the rear of the unit as it slides from
the shelf.

Figure 4-1: Detail of 596B3 Rectifier Position

Continued on next page.