Replacing a 47a converter module, Replacing a 128a converter interface card, Gps2424 replacement procedures, continued – GE Industrial Solutions Galaxy Verification User Manual
Page 82
Galaxy Power System Verification Procedures
4 - 14 Replacement Procedures
Issue 3 January 2008
GPS2424 Replacement Procedures, continued
Replacing a 597A
or 597B Converter
Carrier, continued
Step
Action
4
Turn off the load protectors in the carrier to be replaced and
disconnect the output wiring.
5
To install a converter carrier, slowly slide the carrier into the
shelf until it contacts the rear connector. Remember to
reconnect the carrier cable if two carriers are used.
Turning the Allen key insertion tool clockwise will pull the
carrier into the shelf. See Figure 4-1.
Replacing a 47A
Converter Module
Step
Action
1
Open the converter carrier.
2
Pull the latch forward and remove the old 47A converter
module.
3
Switch new 47A converter module to STBY.
4
Insert new converter module.
5
Switch converter module ON.
Replacing a 128A
Converter
Interface Card
Step
Action
1
Remove the retaining screw that holds the converter interface
card in place.
2
Replace the converter interface card.
3
Replace and tighten the retaining screw.