Galaxy Power System Verification Procedures

Issue 3 January 2008

Replacement Procedures 4 - 5

Memory Backup Battery Replacement for Millennium
Controller

Introduction

The memory backup battery is located on the BSJ (Intelligent
Controller) circuit pack. The battery provides power to retain system
configuration stored in memory in the event the BSJ circuit pack is
removed or input power to the Galaxy Controller is interrupted. Battery
life is typically about five years.

When the memory backup battery is low, the Memory Backup Battery
Low warning is active and the battery should be replaced. Perform the
following three procedures to replace the memory backup battery to
prevent loss of system configuration:

Backup System Configuration

Replace Memory Backup Battery

Restore System Configuration

Backup System

Configuration

Use the EasyView software to perform a backup of the system
configuration. Refer to the discussion of EasyView in Section 4 of this
manual. If you need to install EasyView for the first time, see the
Product Manual “Lineage

®

2000 EasyView Software for the Galaxy

Controller,” Select Code 193-104-105.

DANGER

Danger of explosion or fire if lithium battery is incorrectly
replaced. Replace only with a battery recommended by the
manufacturer. Spare batteries may be ordered per the product
documentation. Lithium batteries may be regulated wastes (due to
reactivity) when disposed of. Always discard used batteries
according to applicable local, state, and federal regulations.

CAUTION

Lithium batteries present risk of fire, explosion, and burns. Do not
recharge, disassemble, heat above 100° C (212° F), or incinerate.
Dispose of used batteries promptly. Keep away from children.