Appendix C - DeviceNet™ to Modbus™ Gateway

C.6.3.

Common Services

Implemented for

Service
Code

Class Level

Instance Level

Service Name

0E

HEX

Yes Yes Get_Attribute_Single

10

HEX

No

Yes

Set_Attribute_Single

C.7. Softstart Object (2D

HEX -

1 Instance)

C.7.1.

Class Attributes (Instance 0)

Attribute
ID

Name DeviceNet

Data Type

Data
Value

Access Rule

1 Revision

UINT 1 Get

C.7.2.

Instance Attributes (Instance 1)

Attribute
ID

Name Data

Type

Data Value

Access
Rule

Modbus Register

3

AtReference

BOOL

See Below

Get

Bit 11: 40257

4 StartMode

USINT

See

Below

Get

/

Set

Will Always be 0

C.7.2.1.

Extended AtReference Values

Value

Extended AtReference Description

0

Not At Reference

1

Output At Voltage Reference

C.7.2.2.

Extended StartMode Values

Value

Extended StartMode Description

0

No Voltage Ramp
No Current Limit

1 Voltage

Ramp

No Current Limit

2

No Voltage Ramp
Current Limit

3 Voltage

Ramp

Current Limit

4 – 9

Reserved

10 - 255

Vendor Specific

C.7.3.

Common Services

Service
Code

Implemented for

Service Name

Class

Level

Instance

Level

0E

HEX

Yes

Yes

Get_Attribute_Single

10

HEX

No

Yes

Set_Attribute_Single

C.8. Control Supervisor Object (29

HEX -

1 Instances)

C.8.1.

Class Attributes (Instance 0)

Attribute
ID

Name DeviceNet

Data Type

Data Value

Access
Rule

1 Revision

UINT

1 Get

C.8.2.

Instance Attributes (Instance 1)

Attribute
ID

Name DeviceNet

Data Type

Data
Value

Access
Rule

Modbus Register