Appendix A - MODBUS RTU Protocol

byte 3: Coil Address High

($00)

byte 4: Coils address Low

($02)

byte 5: No. of Coils High

($00)

byte 6: No. of coils Low

($03)

byte 7: Byte Count

($01)

byte 8: Force Data

($07)

byte 9: CRC_Low

($XX)

byte 10: CRC_High

($XX)


The Normal (if no exception) response is the echo of the Query:

byte 1: Serial Link No.

($20)

byte 2: Function

($0F)

byte 3: Coil Address High

($00)

byte 4: Coils address Low

($02)

byte 5: No. of Coils High

($00)

byte 6: No. of coils Low

($03)

byte 7: CRC_Low

($XX)

byte 8: CRC_High

($XX)


A.11. Discrete Hardwired Inputs (1x References)

The ASTAT-XT incorporates 16 Discrete Inputs, (bit parameters), from which only 6 are operative. The other 10 are
reserved and were incorporated to enable use of word (16 bits) type parameters. Input # is "1 based". The actual
address is 1 lower than input #. For example input #1 is addressed as 0 (10000). The inputs have the following 1x
references:

Input #

Address

ASTAT-XT use Comment


1

0

Stop

Open Input (Input reads" 0") to Stop. (Terminal # 4)
Close Input (Input reads "1") to enable Start / Run.

2

1

Soft Stop

Open Input (Input reads"0") to Soft Stop.

(Terminal # 5)

Close Input (Input reads"1") to enable Start / Run.

3 2 Start

Close

Input

(Input

reads "1") to Start. (Terminal # 6)

4

3

Energy Save *

(Terminal # 7)

Slow Speed *
Reset *

Close Input (Input reads "1") to turn On.
Open Input (Input reads "0") to turn Off.

5

4

Dual Adjust *

(Terminal # 8)

S. Spd Rvrs *
Reset *

Close Input (Input reads "1") to turn On.
Open Input (Input reads "0") to turn Off.

6..7

5 Reserved

8

7

External Fault Open Input = no fault (Input reads" 0") (Terminal #19)

indicates No Fault Condition.

9..16

8..15 Reserved


* Programmable inputs.