3 motor connection and terminals – GE Industrial Solutions ASTAT XT User Manual

Page 75

Advertising
background image

75

• Application diagrams

Beware!
Wrong connection of the ASTAT-XT or the motor may seriously damage the motor or
the ASTAT-XT.

INSIDE DELTA
WARNINGS

When using Inside Delta connection:

It is highly recommended to use a line contactor in order to avoid possible damage

of the motor if the SCR is short circuited in the ASTAT-XT.

If the ASTAT-XT is connected Inside the Delta, motor terminals are “live” (full voltage)

even when the contactor is open.


8.20.3

Motor Connection and Terminals

Motor connection in Delta with no ASTAT-XT.


Note:
Motor terminals are marked as follows:

ASA (USA)

BS

VDE

IEC

T1 - T4

A1-A2

U - X

U1 - U2

T2 - T5

B1-B2

V - Y

V1 - V2

T3 - T6

C1-C2

W - Z

W1 - W2