Types and ratings, 2 nema ratings, Recommended motor and type unit ratings – GE Industrial Solutions ASTAT XT User Manual

Page 9

Advertising
background image

9

• Types and Ratings

2.2

NEMA Ratings

4

. Recommended Motor and Type Unit Ratings.

Light Duty

Nema 10

Normal Duty

Nema 20

Heavy Duty

Nema 30

Type Unit

Current

rating

5

230V 460V 575V Current

rating

6

230V 460V 575V Current

rating

7

230V 460V 575V

A

HP HP HP A HP HP HP A HP HP HP

8

2 5 5 8 2 5 5 8 2 5 5

QTx0008Uxxxx

17 5

10

15

17

5

10

15

12

3

7.5

10

QTx0017Uxxxx

34

10 25 30 31 10 20 25 31 10 20 25

QTx0031Uxxxx

54

20 40 50 44 15 30 40 44 15 30 40

QTx0044Uxxxx

65

20 50 60 58 20 40 50 55 20 40 50

QTx0058Uxxxx

72

25 50 60 72 25 50 60 66 20 50 60

QTx0072Uxxxx

104 40 75 100 85 30 60 75 80 30 60 75

QTx0085Uxxxx

130 50 100 125 105 40 75 100 99 40 75 100

QTx0105Uxxxx

156

60 125 150 145 50 100 150 130 50 100 125

QTx0145Uxxxx

170

60 125 150 170 60 125 150 134 50 100 125

QTx0170Uxxxx

262 100 200 250 210 75 150 200 203 75 150 200

QTx0210Uxxxx

387

150 300 400 310 100 250 300 310 100 250 300 QTx0310Uxxxx

414

150 350 400 390 150 300 400 361 150 300 300 QTx0390Uxxxx

480

200 400 500 460 150 350 400 432 150 350 400 QTx0460Uxxxx

610

250 500

580 200 400 400 552 200 400 500 QTx0580Uxxxx

820

820 250 500 500 690 250 500 QTx0820Uxxxx


Note:
Select the appropriate ASTAT-XT, according to the main power supply and motor voltage rating.
Use QT1xxxxUxxxx units for power supply and motors rated at 230V-500V
Use QT2xxxxUxxxx units for power supply and motors rated at 460V-600V

4

Ratings in Amps. given for ambient temperature up to 40°C and 1000m altitude.

For higher ambient temperature between 40°C and 50°C, derate the current by 2.5% for each °C that is above 40°C.

5

Light duty ratings, only NEMA Class 10 protection is allowed.

6

Normal duty ratings, NEMA Class 10 and 20 protections are allowed.

7

Heavy duty ratings, NEMA Class 10, 20 and 30 protections are allowed