GE Industrial Solutions ASTAT XT User Manual

Page 117

Advertising
background image

117

Appendix C - DeviceNet™ to Modbus™ Gateway

C.9.3.

Common Services

Implemented for

Service
Code

Class Level

Instance Level

Service Name

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set

Attribute

Single

32

HEX

No

Yes

Clear

Counters

C.10. Input Object (70

HEX –

1 Instance)

C.10.1.

Class Attributes (Instance 0)

Attribute
ID

Name DeviceNet

Data Type

Data Value

Access
Rule

1 Revision

UINT

1 Get

C.10.2.

Instance Attributes (Instance 1)

Attribute
ID

Name Description

Access
Rule

Modbus
Address

1

Logic Status

Logic Status of ASTAT-XT:

Get

40257

2

Motor Current

Current, % Im

Get

40258

3

Line Voltage

Line Voltage (Volts)

Get

40259

4

Phase Sequence

1 – Correct Phase Seq.
0 – Wrong Phase Seq.

Get 40260

5 Hardwired

inputs

Get

40261

6 DIP

switch

Get

40262

7 Thermal

Capacity

Get

40293

8 Reserved

Get

40264

9 Reserved

Get

40265

10

Frequency

Main frequency, Hz

Get

40266

11 Thermistor_

Resistance

Thermistor resistance, tenth
Kohm.

Get 40267

12 Reserved

Get

40268

13 Reserved

Get

40269

14 Reserved

Get

40270

15 Reserved

Get

40271

16 Reserved

Get

40272

17 Logic

status

at

power fail

Logic status at control power
supply turns OFF.

Get 40273

18

Elapsed Run Time

Total Hours of motor runs.

Get

40274

19

Number of Starts

Total number of starts

Get

40275

20

Last start period

Duration of last start, Seconds Get

40276

21

Last start peak I

Peak current during last
starting process

Get 40277

22

Time_to_Start

After too many starts trip,
Seconds

Get 40278

23

Total trips

Total number of trips

Get

40279

24

Last Fault number # of the fault that caused trip.

# Fault
01: Over Temperature
02: Short Circuit Current
03: Overload
04: Under Current
05: Under Voltage
06: Over Voltage
07: Phase Loss
08: Phase Sequence

Get 40280