• Control Keypad
•
Verify that all parameters are set correctly.
4.5
Special Actions Performed in Test/Maintenance Mode
4.5.1
Run Self Test
Press the Mode and ▼ keys simultaneously. The LCD will display:
Test/Maintenance
Statistics
Press the Select key. The LCD will display:
Auto Test.
Press UP Key
Press the ▲ key. The LCD will display:
Self Test Passed
And after a few seconds the LCD will display:
Motor Current
0
4.5.2
View Software Version
Press the Mode and ▼ keys simultaneously. The LCD will display:
Test/Maintenance
Statistics
Press the Select key twice. The LCD will display:
Firmware Version
STRT.GE-031208
Press the Mode and ▼ keys simultaneously to exit the Test/Maintenance mode. The LCD will display:
Motor Current
0
4.5.3
Obtain Default Parameters
Press the Mode and ▼ keys simultaneously. The LCD will display:
Test/Maintenance
Statistics
Press the Select key three times. The LCD will display:
Store Settings
Default data
Press the Set + Mode keys simultaneously. The LCD will display:
Data Saved OK
And after a few seconds the LCD will display:
Motor Current
0
CAUTION!
Obtaining Default Data erases all previously modified settings and requires the
operator to reprogram all parameters that differ from the factory default.
Note: It is especially important to reprogram the Starter Current (as shown
on the name plate of the ASTAT-XT), Motor Current and voltage protection
values again.
4.5.4
Reset Statistical Data
Press the Mode and ▼ keys simultaneously. The LCD will display:
Test/Maintenance
Statistics
Press the Select key four times. The LCD will display:
Reset Statistics
Press the Reset + Set keys simultaneously. The LCD will display:
Data Saved OK
And after a few seconds the LCD will display:
Statistical Data
- **** -