1 run self test, 2 view software version, 3 obtain default parameters – GE Industrial Solutions ASTAT XT User Manual

Page 22: 4 reset statistical data

Advertising
background image

22

• Control Keypad

Verify that all parameters are set correctly.


4.5

Special Actions Performed in Test/Maintenance Mode

4.5.1

Run Self Test

Press the Mode and ▼ keys simultaneously. The LCD will display:

Test/Maintenance
Statistics

Press the Select key. The LCD will display:

Auto Test.
Press UP Key

Press the ▲ key. The LCD will display:

Self Test Passed

And after a few seconds the LCD will display:

Motor Current
0


4.5.2

View Software Version

Press the Mode and ▼ keys simultaneously. The LCD will display:

Test/Maintenance
Statistics

Press the Select key twice. The LCD will display:

Firmware Version
STRT.GE-031208

Press the Mode and ▼ keys simultaneously to exit the Test/Maintenance mode. The LCD will display:

Motor Current
0

4.5.3

Obtain Default Parameters

Press the Mode and ▼ keys simultaneously. The LCD will display:

Test/Maintenance
Statistics

Press the Select key three times. The LCD will display:

Store Settings
Default data

Press the Set + Mode keys simultaneously. The LCD will display:

Data Saved OK

And after a few seconds the LCD will display:

Motor Current
0

CAUTION!

Obtaining Default Data erases all previously modified settings and requires the
operator to reprogram all parameters that differ from the factory default.
Note: It is especially important to reprogram the Starter Current (as shown
on the name plate of the ASTAT-XT), Motor Current and voltage protection
values again.

4.5.4

Reset Statistical Data

Press the Mode and ▼ keys simultaneously. The LCD will display:

Test/Maintenance
Statistics

Press the Select key four times. The LCD will display:

Reset Statistics

Press the Reset + Set keys simultaneously. The LCD will display:

Data Saved OK

And after a few seconds the LCD will display:

Statistical Data
- **** -