• Application diagrams

8.10

Energy Save, Slow Speed or Reset

Notes:

Switch D can be used as an Energy

Save/Slow Speed/ Reset

, as

programmed in I/O Programming
Parameters

. Refer to section

4.7.8

page 40.

Energy Save

or Slow Speed

functions require a maintained
contact to operate.

Reset

function requires a momentary

contact to operate

The drawing shows Control Supply and

Control Input from the same source.
Refer to section

8.6 for Control Supply

and Control Input from separate
sources.


8.11

Slow Speed and Slow Speed Reverse

For Slow speed operation:

o

Program Input terminal 7 as
Slow Speed

. Refer to section

4.7.8 page 40.

o

Connect Control Input voltage
to terminal 7 and start the soft
starter. Motor will run at Slow
Speed

.

For Slow speed reverse operation:

o

Program Input terminal 7 as
Slow Speed

. Refer to section

4.7.8 page 40.

o

Program Input terminal 8 as
Slow Speed Reverse

.

Refer to section

4.7.8 page 40.

o

Connect Control Input voltage
to terminal 7 and start the soft
starter. Motor will run at Slow
Speed

. When Control Input

voltage is connected to
terminal 8 motor will stop and
Slow Speed Reverse

.

o

If Control Input voltage is
connected to terminal 8 before
start command, motor will run
at Slow Speed Reverse
when the start command is
initiated.

The drawing shows Control Supply

and Control Input from the same
source. Refer to section

8.6 for Control

Supply and Control Input from
separate sources.