• Trouble Shooting


7.

TROUBLE SHOOTING

Upon fault – motor stops, the Fault LED lights and Fault Relay chances position. The LCD shows TRIP: < fault
description>. (for example: Trip: Undercurrent).

Storage Error

Storage Error displays in case of a failure in parameter storing.
Wait 3 seconds and try to store again.
If does not help, load the default parameters of the ASTAT-XT and re-program all
parameters.
To obtain default parameters refer to section

4.5.3 page 22.

Access Locked

Avoids parameter changing when dip switch # 8 –Software Lock is set to ON.
If parameter changing is required verify that dip switch #8 is set to OFF.
For Dip switch #8 setting refer to section

5.5.6 page 50.

Thermistor Trip

Trips the ASTAT-XT when the motor thermistor resistance decreases below trip level
set.
Check resistance of the thermistor and cables; Check motor temperature near
thermistor location.
For Thermistor Trip protection setting refer to section

4.7.7 page 38.

Too Many Starts

Trips the ASTAT-XT if the number of starts, during Duty Cycle Time
exceeds the preset number.
Wait until motor and ASTAT-XT cool down – according to Number Of Starts,
Duty Cycle Time

and Start Lockout settings. Refer to section

4.7.3

page 32.

Long Start Time

Trips the ASTAT-XT if output voltage does not reach nominal at the preset Max.
Start time.

Check Starter Current and Max. Start Time settings. Increase Starting
Voltage, Current Limit

& Max. Start Time or decrease Ramp UP

Time

as necessary.

For start Settings Parameters refer to section

4.7.3 page 32.

O/C JAM Fault

Trips the ASTAT-XT when:

Instantaneously when current exceeds 8.5 x ASTAT-XT Current

During starting when current exceeds 8.5 x Motor Current

During running when current exceeds 200-850% of Motor Current.

O/C JAM Fault

has a programmable delay of 0-5 seconds where the ASTAT-XT

detects the fault and does not trip before time delay has elapsed (delay is overriden
when current reaches 8.5 x ASTAT-XT Current).

Check that motor is not stalled or jammed.
Check Motor Current and Starter Current settings.
Check motor and cable connections.
Perform a “Megger” test to verify motor and cable’s condition.
For protection parameters settings refer to section

4.7.2 page 27.

CAUTION

Check that “Megger” maximum voltage is no more than 500V!
Disconnect terminal 21 before performing a “Megger” test.

Overload

Trips the ASTAT-XT when current exceeds the Overload Trip level and the thermal
register has filled up.
Check Motor Current, Starter Current settings and overload settings and
check motor current, then wait at least 15 minutes to let the motor and ASTAT-XT
cool down before restarting.
For protection parameters settings refer to section

4.7.2 page 27.