• Starting Procedure


Continued from previous page























6.2

Examples of Starting Curves

6.2.1

Light Loads - Pumps, Etc.

(In these cases the actual current is always lower than the Current Limit setting)
Starting Voltage-

set to 30%

Current Limit

-

set to 300-350%

Ramp UP Time

-

set to 10 sec.


Upon start, the voltage quickly increases to the Starting Voltage value (30% of Un) and then gradually ramps-
up to nominal.
The current will simultaneously increase to peak current value (lower than the Current Limit setting), before
smoothly decreasing to the operating current.

6.2.2

High Inertia Loads: Crushers, Centrifuges, Mixers, Etc.

(In these cases the actual current is at the CURRENT LIMIT setting during part of the starting time)
Starting Voltage–

set 40%

Current Limit–

set 400%

Ramp UP Time

set 3 sec

Check Last Start Time and set Max. Start time to approximately 5 seconds

longer than the Last Start Time.

For future reference it is advised to keep records of the following parameters in the

Statistical Data:
Last Start Time:
Last Start Curr.:

Motor acceleration

time to full speed is

as required?

No

Yes

If acceleration time is too short, increase Ramp
UP Time

setting and/or decrease Current

Limit

setting (when decreasing Current

Limit

, make sure that the motor increases

speed gradually and does not stall).

A

Apply the START command