• Control Keypad


4.7.11

Comm. Parameters

42

– Page 8 – With the DeviceNet Optional PCB

Function &

Default

Range

Unit

Description

COMM. PROTOCOL
DeviceNet

Profibus/
Modbus/
DeviceNet

Sets ASTAT-XT’s communication protocol.
Operational when the optional communication PCB is
installed.

Baud Rate

Set Manually

Set

the Baud Rate by changing the position of the

rotary switches on the optional PCB as shown on section

C.1.5 page 109.

Parity Check
AUTO (DeviceNet)

User can not change Parity Check value.

DeviceNet ID
Set Manually

Set the unit ID by changing the position of the rotary
switches on the optional PCB as shown on section

C.1.5

page 109.

S. Link Par. Set
Disabled

Enabled/
Disabled

Enables parameter modification via serial
communication

Ser. Link Control
Disabled

Enabled/
Disabled

Enables start, stop, reset etc. via serial communication

Store Settings
COMM. Parameters

Enabled/
Disabled

Same

as

Store Settings Main Settings

on

page 28.
Note:
After changing communication parameters and storing
them, control power must be switched OFF and ON to
load new communication parameters.