Appendix A - MODBUS RTU Protocol

APPENDIX A - MODBUS RTU PROTOCOL
A.1. Introduction

This document summarizes the serial link protocol to / from the DIGITAL SOFT STARTER(ASTAT-XT).

Features:

RS485 Hardware.

Asynchronous serial link.

Half duplex.

Format: Modbus RTU Mode (Remote Terminal Unit Mode).

o

Binary

o

Each character contains 11 bits:
- One start bit
-8 data bits, least significant bit sent first.
- 1 Parity bit. Even / Odd / No can be selected.
- 1 Stop bit if Parity is used, 2 stop bits if Parity is not used.

o

Cyclical Redundancy Check (CRC), 16 bits.

Baud Rates: 1200 / 2400 / 4800 / 9600 bits per second.

Response time of the ASTAT-XT:

o

Normally, 4ms <= time response <= 40mS.

o

For a long response, time response <= 200mS.

It is not recommended to transmit to the ASTAT-XT at a rate higher than once per second because this can slow

down ASTAT-XT response times.

After storing parameter settings, there is a 1 sec. time period during which transmission to the same ASTAT-XT is

forbidden.

Broadcast commands: not supported.


Notes:
*

It is recommended that you connect 120 OHM resistors to both ends of the serial link.

*

You must turn OFF (and ON again) power to the controller after changing Baud_Rate, Parity_Check or

Serial_Link_No (Slave Address). These parameters can only be modified manually and not through the Serial Link.

WARNING

You must connect earth to the ASTAT-XT earth screw before connecting serial link wires.
Ignoring this instruction may result in permanent damage to the Serial Link Hardware
and might result in death or serious injury.