9 auto reset, 9 timing occurrence table – GE Industrial Solutions ASTAT XT User Manual

Page 46

Advertising
background image

46

• Control Keypad

4.8.9

Auto Reset

Undervoltage

and Phase Loss faults can auto-reset (refer to section

4.7.7 on page 38). The ASTAT-XT will reset

itself 60 seconds after voltage was fully restored, provided that the START signal is removed.

Undercurrent

fault can be set to auto-reset (refer to section

4.7.7 on page 38).

The ASTAT-XT will reset itself when a programmed time delay has elapsed, even if the START signal is not removed.

4.9

Timing Occurrence Table

Active During

Timing And Occurrence

Start

Run

Stop

Soft
Stop

Too many starts with Start Lockout period

Electronic overload with curve selection

O/C JAM Fault
ASTAT-XT protection – trip immediately at I≥850% Starter
Current

Motor protection – trip function
During start – factory set at 850% Motor Current after O/C
JAM Delay.

During run – adjustable 200 – 850% Motor Current after O/C
JAM Delay.

Undercurrent adjustable time delay

Phase Loss

Phase Sequence

Undervoltage with adjustable time delay. Time delay is
override in case of Phase Loss.

Overvoltage with adjustable time delay

Long start time (stall protection)

Shorted SCR

Wrong Connection (load loss)

External fault – input from a N.O. contact

SCR protection by Metal Oxide Varistors (MOV)

ASTAT-XT over-temperature

ASTAT-XT internal test, when the On LED is lit.

Motor thermistor – programmable PTC/NTC, with adjustable
trip level.